Voltage Drop and Cable Size Calculator (mm² and AWG)
Enter the current, the one-way cable length, the conductor material and size, and the supply voltage. See the voltage drop in volts and percent, the voltage left at the load, and the smallest conductor area that keeps the drop within your limit.
This checks voltage drop only. It does not check how much current the cable can safely carry (ampacity), its protection or installation conditions; your electrical code's tables decide the minimum cable size.
- Voltage drop (V)
- –
- Voltage drop (%)
- –
- Voltage at the load
- –
- Smallest area for the drop limit only (mm²)
- –
- Smallest area for the drop limit only (kcmil)
- –
- Smallest AWG for the drop limit only
- –
- Resistance of one conductor, one way
- –
Assumptions
- Resistance only: cable reactance and power factor are not included, which suits small cables; large cables and motors drop more.
- Single phase and DC count both wires (2 × current × resistance); balanced three phase uses √3.
- Resistance grows with temperature in a straight line from the 20 °C value, as NBS Handbooks 100 and 109 give it.
- Solid round conductors of the stated area; stranding, joints and terminations are not modelled.
Estimate Checked 29 October 2026 Michigan State University, Electrical Tech Note 227: Voltage Drop (2009): Eq. 227.1, 227.2, 227.9, 227.12 and 227.13, K at 50 °C, 5% recommendation; its 4 AWG and 80 A feeder examples are tests here All sources
How it is calculated
- Resistivity at T = resistivity at 20 °C × (1 + α × (T − 20)): copper 0.017241 Ω·mm²/m, α 0.00393; aluminium 0.028264, α 0.00403
- Resistance of one conductor (Ω) = resistivity × one-way length (m) ÷ area (mm²)
- Voltage drop = 2 × current × resistance (single phase or DC); √3 × current × resistance (three phase)
- Drop % = voltage drop ÷ supply voltage × 100; voltage at the load = supply − drop
- Smallest area = 2 (or √3) × resistivity × current × length ÷ (allowed % ÷ 100 × supply voltage)
- AWG: No. 0000 = 0.4600 in, No. 36 = 0.0050 in, sizes between in geometric progression; area in cmil = (diameter in mils)²
Worked example
A 16 A single-phase circuit, 20 m of 2.5 mm² copper, at 230 V and 50 °C.
| You enter | |
|---|---|
| Circuit | Single phase or DC (two wires) |
| Current | 16 A |
| Cable length, one way | 20 |
| Length unit | Metres (m) |
| Conductor | Copper |
| Conductor size | Type the area in mm² below |
| Conductor area | 2.5 mm² |
| Supply voltage | 230 V |
| Allowed voltage drop | 5 % |
| Conductor temperature | 50 °C |
| You get | |
| Voltage drop (V) | 4.93 V |
| Voltage drop (%) | 2.15 % |
| Voltage at the load | 225.1 V |
| Smallest area for the drop limit only (mm²) | 1.07 mm² |
| Smallest area for the drop limit only (kcmil) | 2.12 kcmil |
| Smallest AWG for the drop limit only | 16 AWG |
| Resistance of one conductor, one way | 0.1542 Ω |
16 A over 20 m drops 4.93 V (2.15%), leaving 225.1 V at the load. That is within your 5% limit; for voltage drop alone the conductor needs at least 1.07 mm². The current rating in your code may need a larger cable; use whichever is larger.
Questions
Why is the length one way?
The current goes out on one wire and comes back on the other, so the formula already multiplies by 2 for single phase and DC. In balanced three phase the return currents largely cancel, so the multiplier is √3 (Michigan State rounds it to 1.73).
Why does the temperature matter?
Copper and aluminium resist more when hot: copper about 0.4% more for each degree. A cable at 50 °C has about 12% more resistance than at 20 °C, so it drops more voltage.
Sources and checks
- Michigan State University, Electrical Tech Note 227: Voltage Drop (2009): Eq. 227.1, 227.2, 227.9, 227.12 and 227.13, K at 50 °C, 5% recommendation; its 4 AWG and 80 A feeder examples are tests here
- NBS Handbook 100 (1966), Copper Wire Tables: annealed copper 0.017 241 Ω·mm²/m at 20 °C, temperature coefficient 0.00393, American Wire Gage definition
- NBS Handbook 109 (1972), Aluminum Wire Tables, Table 1: EC-H19 aluminium 0.028 264 Ω·mm²/m at 20 °C, temperature coefficient 0.00403
Last checked: 29 October 2026. This tool passes 8 automatic tests before every release. How we check our tools
Cite this page
Voltage Drop and Cable Size Calculator (mm² and AWG). GlanceDesk Compute. Last checked 29 October 2026. https://glancedeskcompute.com/
Your numbers stay on your device unless you share them.
Voltage drop is one check among several. Cable size must also meet the current rating, protection and installation rules of your electrical code (for example IEC 60364-5-52 or your national wiring rules). Ask a qualified electrician. Results are estimates for planning and learning. They are not a design check and do not replace a qualified engineer or your local building/electrical code.