Data Centre PUE and Cooling Load Calculator
Enter the total power drawn by the facility and the power drawn by the IT equipment. See the Power Usage Effectiveness (PUE), its inverse DCiE, and the IT heat load in kW, BTU per hour and tons of refrigeration.
An estimate for planning. PUE is properly reported from energy measured over a year; a single pair of power readings gives a snapshot. The heat figures take all IT power as heat in the room, and do not size a cooling system.
- Power Usage Effectiveness (PUE, a ratio)
- –
- DCiE (IT share of total)
- –
- Power not used by IT (cooling, losses, lighting)
- –
- Heat from the IT load (kW)
- –
- Heat from the IT load (BTU/h)
- –
- Heat from the IT load (TR)
- –
Assumptions
- Both readings cover the same time and the same site.
- All electrical power used by the IT equipment ends up as heat in the room.
- Heat in BTU/h and tons of refrigeration uses the NIST SP 811 factors (1 BTU/h = 0.2930711 W; 1 ton = 12,000 BTU/h).
Estimate Checked 3 November 2026 The Green Grid, White Paper #49: PUE, A Comprehensive Examination of the Metric (2012), hosted by Lawrence Berkeley National Laboratory All sources
How it is calculated
- PUE = total facility energy ÷ IT equipment energy (The Green Grid; ISO/IEC 30134-2); with power readings, total facility power ÷ IT equipment power (minimum 1.0)
- DCiE = 1 ÷ PUE = IT equipment power ÷ total facility power
- Heat (BTU/h) = IT power (W) ÷ 0.2930711
- Tons of refrigeration = IT power (W) ÷ 3,516.853 (1 ton = 12,000 BTU/h)
Worked example
A site drawing 1,500 kW in all, of which 1,000 kW goes to IT equipment.
| You enter | |
|---|---|
| Total facility power | 1,500 kW |
| IT equipment power | 1,000 kW |
| You get | |
| Power Usage Effectiveness (PUE, a ratio) | 1.5 |
| DCiE (IT share of total) | 66.67% |
| Power not used by IT (cooling, losses, lighting) | 500 kW |
| Heat from the IT load (kW) | 1,000 kW |
| Heat from the IT load (BTU/h) | 3,412,141 BTU/h |
| Heat from the IT load (TR) | 284.35 TR |
For every kW the IT equipment uses, the site draws 1.5 kW in all, so 66.67% of the power reaches IT. The IT load gives off about 3,412,141 BTU/h of heat, or 284.35 tons of refrigeration.
Questions
Should I use power (kW) or energy (kWh)?
The Green Grid defines PUE on energy and asks for the yearly average. Power readings work too but give a snapshot. You can type kWh for both boxes over the same period: PUE and DCiE stay correct, but then ignore the heat figures.
What is a good PUE?
The lowest possible is 1.0, when every unit of power reaches the IT equipment. The Green Grid paper notes 1.6 or better as achievable with proper design.
Sources and checks
- The Green Grid, White Paper #49: PUE, A Comprehensive Examination of the Metric (2012), hosted by Lawrence Berkeley National Laboratory
- ISO/IEC 30134-2, Data centres key performance indicators, Part 2: Power usage effectiveness (PUE), edition 2 (2026)
- NIST SP 811 (2008), Appendix B.9: British thermal unit per hour and ton of refrigeration (12,000 Btu/h) in watts
Last checked: 3 November 2026. This tool passes 5 automatic tests before every release. How we check our tools
Cite this page
Data Centre PUE and Cooling Load Calculator. GlanceDesk Compute. Last checked 3 November 2026. https://glancedeskcompute.com/
Your numbers stay on your device unless you share them.
An estimate for planning and learning. It is not a PUE audit, an ISO/IEC 30134-2 report or a cooling design, and does not replace a qualified engineer. Results are estimates for planning and learning. They are not a design check and do not replace a qualified engineer or your local building/electrical code.