Battery Backup Time Calculator (UPS, Inverter, Solar)

W
Add up the watts of everything the battery will run at the same time (fans, lights, router, TV, pump).

The numbers filled in are examples. Type your own.

V
From the battery label, for example 12 V.
Ah
The amp-hour (Ah) rating on the battery label.
With one battery, either choice gives the same answer.
%
Use the figure on your inverter's data sheet. The 85% example is from a worked example in Sandia report SAND2001-0674. Enter 100 if the load runs on DC straight from the battery.
%
100% uses all of the rated amp-hours. If the battery maker advises a lower limit, enter it here.
h
The hours the Ah rating is given for, often printed as C20 (20 h) or C10 (10 h). Kuphaldt notes that a rating with no time stated is usually taken as 8 h.

Enter the load in watts, the battery voltage and amp-hours, how many batteries and how they are connected, and the inverter efficiency. See roughly how long the battery bank can run the load, and whether the load draws more current than the battery is rated for.

An estimate from the battery's rated amp-hours. Real batteries give less when they are old, cold or discharged quickly. Battery makers often advise against using the full capacity; check the data sheet.

Backup time
–
Backup time in hours and minutes
–
Current drawn from the battery bank
–
Current the Ah rating is given for
–
Energy stored in the bank
–
Battery bank voltage
–
Battery bank capacity
–

Assumptions

  • Batteries in series add their voltages; batteries in parallel add their amp-hours. All batteries are the same.
  • Current from the bank = load ÷ (efficiency × bank voltage); backup time = usable amp-hours ÷ that current.
  • The rated amp-hours hold at the rated discharge time; at higher currents real batteries give less.
  • The load is steady. Battery age, temperature and charge level are not modelled.

Estimate Checked 29 October 2026 Kuphaldt, Lessons in Electric Circuits Vol. I (LibreTexts) 11.3: Battery Ratings (time = amp-hours ÷ current; its 70 Ah examples are tests here) All sources

How it is calculated

  • Series: bank voltage = number × voltage, bank Ah = Ah of one battery. Parallel: bank Ah = number × Ah, voltage unchanged
  • Energy stored (Wh) = bank voltage × bank Ah (from P = I × E)
  • Battery current (A) = load (W) ÷ (efficiency × bank voltage)
  • Backup time (h) = bank Ah × usable share ÷ battery current (Kuphaldt: time = amp-hours ÷ current)
  • Current the rating is given for (A) = bank Ah ÷ rated discharge time; above it, expect less time

Worked example

One 12 V, 150 Ah battery running 300 W through an inverter at 85% efficiency.

You enter
Load300 W
Voltage of one battery12 V
Capacity of one battery150 Ah
Number of batteries1
How they are connectedIn series (voltages add, for example 2 × 12 V = 24 V)
Inverter or UPS efficiency85 %
Share of the capacity you will use100 %
Rated discharge time of the battery20 h
You get
Backup time5.1 h
Backup time in hours and minutes5 h 6 min
Current drawn from the battery bank29.41 A
Current the Ah rating is given for7.5 A
Energy stored in the bank1,800 Wh
Battery bank voltage12 V
Battery bank capacity150 Ah

A 12 V, 150 Ah battery bank stores 1,800 Wh. Running 300 W, it lasts about 5 h 6 min on paper. The load draws 29.41 A, more than the 7.5 A the rating is given for, so expect noticeably less time: batteries give fewer amp-hours at high currents. This uses the full rated capacity; battery makers often advise using less, so check your battery's data sheet.

Questions

Why is my real backup time shorter?

The amp-hour rating holds only at the current it was tested at, often over 20 hours. Kuphaldt explains that at high currents a battery runs flat sooner, and age and cold reduce capacity too. The tool flags when your load draws more than the rated current.

Do series and parallel give different backup times?

Not for the same batteries: two 12 V, 100 Ah batteries store 2,400 Wh either way. Series gives 24 V at 100 Ah, parallel 12 V at 200 Ah. The current drawn changes, which matters for the rating check and for cable size.

Sources and checks

Last checked: 29 October 2026. This tool passes 8 automatic tests before every release. How we check our tools

Cite this page

Battery Backup Time Calculator (UPS, Inverter, Solar). GlanceDesk Compute. Last checked 29 October 2026. https://glancedeskcompute.com/battery-backup-time-calculator/

Found a wrong number? Tell us

Your numbers stay on your device unless you share them.

For choosing a UPS, inverter or battery bank, follow the equipment data sheets and your electrical code, and ask a qualified electrician. Battery cables and fuses must be sized for the current shown. Results are estimates for planning and learning. They are not a design check and do not replace a qualified engineer or your local building/electrical code.