Battery Backup Time Calculator (UPS, Inverter, Solar)
Enter the load in watts, the battery voltage and amp-hours, how many batteries and how they are connected, and the inverter efficiency. See roughly how long the battery bank can run the load, and whether the load draws more current than the battery is rated for.
An estimate from the battery's rated amp-hours. Real batteries give less when they are old, cold or discharged quickly. Battery makers often advise against using the full capacity; check the data sheet.
- Backup time
- –
- Backup time in hours and minutes
- –
- Current drawn from the battery bank
- –
- Current the Ah rating is given for
- –
- Energy stored in the bank
- –
- Battery bank voltage
- –
- Battery bank capacity
- –
Assumptions
- Batteries in series add their voltages; batteries in parallel add their amp-hours. All batteries are the same.
- Current from the bank = load ÷ (efficiency × bank voltage); backup time = usable amp-hours ÷ that current.
- The rated amp-hours hold at the rated discharge time; at higher currents real batteries give less.
- The load is steady. Battery age, temperature and charge level are not modelled.
Estimate Checked 29 October 2026 Kuphaldt, Lessons in Electric Circuits Vol. I (LibreTexts) 11.3: Battery Ratings (time = amp-hours ÷ current; its 70 Ah examples are tests here) All sources
How it is calculated
- Series: bank voltage = number × voltage, bank Ah = Ah of one battery. Parallel: bank Ah = number × Ah, voltage unchanged
- Energy stored (Wh) = bank voltage × bank Ah (from P = I × E)
- Battery current (A) = load (W) ÷ (efficiency × bank voltage)
- Backup time (h) = bank Ah × usable share ÷ battery current (Kuphaldt: time = amp-hours ÷ current)
- Current the rating is given for (A) = bank Ah ÷ rated discharge time; above it, expect less time
Worked example
One 12 V, 150 Ah battery running 300 W through an inverter at 85% efficiency.
| You enter | |
|---|---|
| Load | 300 W |
| Voltage of one battery | 12 V |
| Capacity of one battery | 150 Ah |
| Number of batteries | 1 |
| How they are connected | In series (voltages add, for example 2 × 12 V = 24 V) |
| Inverter or UPS efficiency | 85 % |
| Share of the capacity you will use | 100 % |
| Rated discharge time of the battery | 20 h |
| You get | |
| Backup time | 5.1 h |
| Backup time in hours and minutes | 5 h 6 min |
| Current drawn from the battery bank | 29.41 A |
| Current the Ah rating is given for | 7.5 A |
| Energy stored in the bank | 1,800 Wh |
| Battery bank voltage | 12 V |
| Battery bank capacity | 150 Ah |
A 12 V, 150 Ah battery bank stores 1,800 Wh. Running 300 W, it lasts about 5 h 6 min on paper. The load draws 29.41 A, more than the 7.5 A the rating is given for, so expect noticeably less time: batteries give fewer amp-hours at high currents. This uses the full rated capacity; battery makers often advise using less, so check your battery's data sheet.
Questions
Why is my real backup time shorter?
The amp-hour rating holds only at the current it was tested at, often over 20 hours. Kuphaldt explains that at high currents a battery runs flat sooner, and age and cold reduce capacity too. The tool flags when your load draws more than the rated current.
Do series and parallel give different backup times?
Not for the same batteries: two 12 V, 100 Ah batteries store 2,400 Wh either way. Series gives 24 V at 100 Ah, parallel 12 V at 200 Ah. The current drawn changes, which matters for the rating check and for cable size.
Sources and checks
- Kuphaldt, Lessons in Electric Circuits Vol. I (LibreTexts) 11.3: Battery Ratings (time = amp-hours ÷ current; its 70 Ah examples are tests here)
- Kuphaldt, Lessons in Electric Circuits Vol. I (LibreTexts) 2.4: Calculating Electric Power (P = I × E)
- Sandia National Laboratories, SAND2001-0674 (Wiles, 2001): Photovoltaic Power Systems and the National Electrical Code, Stand-Alone Systems: Inverters (2,500 W at 85% efficiency and 22 V draws 134 A)
Last checked: 29 October 2026. This tool passes 8 automatic tests before every release. How we check our tools
Cite this page
Battery Backup Time Calculator (UPS, Inverter, Solar). GlanceDesk Compute. Last checked 29 October 2026. https://glancedeskcompute.com/
Your numbers stay on your device unless you share them.
For choosing a UPS, inverter or battery bank, follow the equipment data sheets and your electrical code, and ask a qualified electrician. Battery cables and fuses must be sized for the current shown. Results are estimates for planning and learning. They are not a design check and do not replace a qualified engineer or your local building/electrical code.